When Two Transformer Incomers Have Different Power Quality Problems.

Industry: Cement Manufacturing
Application: Industrial Power Distribution
Solution: RTPFC + Active Harmonic Filter
 
A cement manufacturing plant was experiencing low power factor and harmonic distortion at two transformer incomers. At first, the requirement seemed straightforward: improve the plant’s electrical performance.
 
But there was an important question to answer first: Were both transformers actually facing the same problem?
 
Clariant Power set out to find that out.
 
It Started With the Measurements
 
We conducted a detailed Power Quality Analysis using a Fluke Power Quality Analyzer at both transformer incomers.
 
The study measured key electrical parameters including power factor, current, VTHD and ATDD. The results showed that the two incomers had noticeably different conditions. At Transformer 1, the power factor was 0.85, with ATDD at 7.2%. At Transformer 2, the power factor was lower at 0.77, while ATDD reached 35.3%. That difference was important. It meant that simply applying the same corrective configuration to both transformers would not address the actual requirement. The Measurements Shaped the Engineering Based on the conditions identified during the analysis, we configured the solution for each transformer. Transformer 1 715 kVAr, 525 V RTPFC Panel The RTPFC panel was configured to address the power factor requirement identified at the incomer.
 
  1. Transformer 2 715 kVAr, 525 V RTPFC Panel + 200 A + 300 A Active Harmonic Filter Here, the significantly higher harmonic distortion called for additional harmonic mitigation alongside power factor correction. The solution was therefore not based on a standard configuration. It was based on what the measurements showed. Then We Measured Again After implementation, the electrical parameters were measured again to verify the improvement. Parameter Transformer 1 Transformer 2 Power Factor 0.85 → 0.99 0.77 → 0.99 Current 1432 A → 1221 A 1034 A → 800 A VTHD 2.5% → 1.9% 5.4% → 4.2% ATDD 7.2% → 5.9% 35.3% → 7.4% The most significant improvement was seen at Transformer 2. Its power factor improved from 0.77 to 0.99, while current harmonic distortion reduced from 35.3% to 7.4%. Across both transformer incomers, the case study reports that voltage and current harmonic distortion were brought within IEEE-519 limits after implementation. One Plant. Two Conditions. One Measurement Led Approach. This project shows why power quality correction cannot always be approached with a one size fits all configuration. The two transformer incomers were part of the same plant, but their electrical conditions were different. Clariant Power’s approach was simple: Measure the condition. Understand the requirement. Engineer the solution. Measure the result. Project Snapshot Industry: Cement Manufacturing Application: Transformer Incomers Solution: RTPFC + Active Harmonic Filter Power Factor: Up to 0.99 ATDD at Transformer 2: 35.3% → 7.4% Facing a similar power quality requirement? Talk to Clariant Power’s engineering team.

Get in Touch

Your email address will not be published. Required fields are marked
Product Enquiry

The Future of Industrial Electricity Is About Better Management

Renewable energy is changing industrial power management. Discover why factories need to look beyond energy generation to power quality, stability and efficient electricity management.

Power GRid
Address Company

799/A, Clariant House, Abhijeet Court, Bhandarkar Road, Pune-411004.

Phone: +91 9130057668 , 020-67332999

Email: sales@clariantindia.co.in

It's all about saving your money!

+91-20-67332999

sales@clariantindia.co.in

799/A, Clariant House, Abhijeet Court, Bhandarkar Road,
Pune-411004.

Monday-Saturday: 10am –  7pm

© Clariant Power System Ltd. 2024, All Rights Reserved.