Clariant Power System Ltd.

Power quality case study · Industrial Effluent Treatment

Power Quality Improvement in an Industrial Effluent Treatment Plant

ApplicationIndustrial Effluent Treatment Plant
Study location22kV HT Grid & Transformer Incomers
SolutionAHPFC + Tuned Filters + Active Harmonic Filter

The power factor looked fine. The electrical system wasn't.

At an industrial effluent treatment plant, the power factor was already around 0.98 lag.

Yet the plant was experiencing failures of electronic cards and concerns around harmonic distortion across its electrical network.

At the main 22kV HT grid incomer, current harmonic distortion measured 18.9%.

The question was no longer just how to improve power factor.

It was to understand what was happening within the electrical system.

The measurements told a different story.

Clariant Power carried out a detailed power-quality study using a Fluke 435 Harmonic Analyzer.

Measurements were taken at the main 22kV HT grid incomer and major transformer incomers under operating conditions, covering power factor, voltage harmonic distortion, current harmonic distortion, load current and individual harmonic components.

The study showed that the issue varied across the plant.

At the Old Pump House Transformer

Power Factor0.99 lag
VTHD6.4%
ATHD23.1%

At the Final Blower Transformer

Power Factor0.98 lag
VTHD6.9%
ATHD37.2%

There was another important part of the picture.

The existing capacitor banks were installed without series reactors. While they were helping improve power factor, their configuration was also creating a low-impedance path for harmonic currents and contributing to harmonic amplification.

The plant therefore needed more than conventional power-factor correction.

The solution had to change with the conditions.

The measurements showed that a single configuration would not address the requirements across the plant.

Clariant Power designed the solution around the electrical conditions at each transformer.

Old Blower Transformer

Transformer capacity

2 MVA

800 kVAr525V AHPFC with Tuned Filter Reactors

New Blower Transformer

Transformer capacity

2.5 MVA

900 kVAr525V AHPFC with Tuned Filter Reactors

Final Pump House Transformer

Transformer capacity

2 MVA

150 kVAr525V AHPFC with Tap Tuned Filter Reactors+ 150 Amp Active Harmonic Filter

The configurations were selected based on the conditions identified during the power-quality study.

Then the numbers changed.

Following implementation, Clariant Power conducted another round of harmonic analysis at the main 22kV HT grid incomer.

ParameterBeforeAfter
Power Factor0.98 lag1.00
Voltage Harmonic Distortion2.4%1.5%
Current Harmonic Distortion18.9%4.1%

The overall power factor was subsequently recorded at 0.995 lag, while voltage and current harmonic distortion were brought within the specified limits.

The improvement also reflected in the power factor incentive.

Before implementation, the plant recorded an average monthly power factor of 0.983 lag, with a 1.65% power factor incentive.

Following implementation, the average power factor increased to 0.995 lag, with the incentive increasing to 2.25%.

October 2016

Average PF0.983 lag
Incentive1.65%

November 2016

Average PF0.995 lag
Incentive2.25%

Understanding the system changed the solution.

The plant already had power-factor correction.

What it needed was a solution that addressed the actual conditions within its electrical network.

Clariant Power measured the system, identified the harmonic conditions, engineered the required configurations and verified the improvement after implementation.

The Result:

  1. Improved Power Factor.
  2. Reduced Harmonic Distortion
  3. Measurable improvement in overall power quality.
Clariant Power industrial installation

Project Snapshot

Industry Effluent Treatment Plant
ApplicationPower Quality & Harmonic Mitigation
SolutionAHPFC with Tuned Filter Reactors and Active Harmonic Filter%
Key Outcome18.9% → 4.1%
Current harmonic distortion at the main grid incomer

Facing power-quality challenges in your plant?

Understand the problem before choosing the solution.

Talk to Clariant Power.

Contact Engineering Team

It's all about saving your money!

+91-20-67332999

sales@clariantindia.co.in

799/A, Clariant House, Abhijeet Court, Bhandarkar Road,
Pune-411004.

Monday-Saturday: 10am –  7pm

© Clariant Power System Ltd. 2024, All Rights Reserved.